aobo

ABDT-LUB Vortex Flowmeter Flange Installation with Display

Vortex flowmeters accurately measure the flow of gases, liquids and steam over a wide range of temperatures


Characteristics

Diameter:DN15-DN800/ ½…32″
Process temperature:-40°C to 420°C /-40°F to 788°F
Max process pressure:PN100/1450 psig
Accuracy:1.0%,1.5%
Output signal:Pulse,frequency,4-20mA,RS485 Modbus,HART
Flange:GB/ANSI/ASME/DIN/JIS Std

 

 

Overview

Vortex flow meters are good choice in steam-related applications including steam measurement for district energy systems and industrial plants.It also excel for a variety of applications across a wide range of industries including oil and gas, steel and metal , chemical and Pulp and paper, and food and beverage.

Features

  • For liquids, (wet) gases, saturated and superheated steam (+420°C / +788°F)
  • Wide flow range (1:15)
  • Standard measurement accuracy: ±1%-±1.5% of Reading
  • No moving parts to maintain or repair,easy installation
  • Low power consumption,lower pressure loss,good repeatability and stability
  • Long-term stability drift-free Piezoelectric sensors
  • Pressure pipe container special equipment license and Explosion-proof
  • High definition backlight display, English menu, easy to use and access
  • Pulse and frequency signal, 4-20 mA HART, RS 485 communication

Measuring principle

Vortex

Measured media

Liquids, Gases, Steams

Nominal diameter range

DN15-DN800(½-32″)

Measured variables

Volume flow, corrected volume flow, temperature

Accuracy

±1%, ±1.5% of Reading

Measuring range

Liquid: 0.5m³/h to 8000 m³/h

Steam,gas: 5m³/h to 80000 m³/h

Max nominal pressure

PN100

Max medium temperature

+420°C / +788°F

Ambient temperature range

-40 to +55°C

Protection

IP65, IP68

Flange standard

GB/ASME/ANSI/DIN/JIS Std

Display/Operation

4-line backlit display with touch control, local display

Outputs

Pulse, 4-20mA, Frequency

Inputs

PT100/PT1000

Communication

HART,RS485 Modbus

Power supply

DC(12~24)V, DC3.6V battery

Dual power(DC24V and DC3.6V baterry)

Explosion-proof

Ex db IIC T6 Gb

          

Products

Model No

Manual

Vortex Flowmeter Wafer Installation without Display-Brochure
LUGBXXXXDT
Vortex Flowmeter Flange Installation without Display-Brochure
LUGBXXXXDT
Vortex Flowmeter Wafer Installation with Display-Brochure
LUBXXXXDT
Vortex Flowmeter with Temperature & Pressure Compansation-Brochure
LUBXXXXDT
Vortex Flowmeter Flange Installation with Display-Brochure
LUBXXXXDT

Contact Us

* The marked fields are mandatory

Need more information?

Contact us for more details about inquiry,solutions and services